EasyManua.ls Logo

Siemens Simantic ET 200S - Page 186

Siemens Simantic ET 200S
274 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Analog electronic modules
4.10 4AI I 2WIRE Standard analog electronic module (6ES7134-4GD00-0AB0)
ET 200S
4-56 Manual, Edition 10/2005, A5E00514527-01
Suppression of interference, limits of error
Interference voltage suppression for f = n x (f1
± 1%), (f1 = interference frequency)
Common mode interference
(peak value of interference < rated value of
input range)
min. 70 dB
Crosstalk between the inputs min. -50 dB
Operational limit
(in the entire temperature range, with reference
to the input range)
± 0.4%
Basic error limit (operational limit at 25° C with
reference to input range)
± 0.3%
Temperature error (with reference to the input
range)
± 0.003 %/K
Linearity error (with reference to the input range) ± 0.01%
Repeatability
(in steady state at 25° C with reference to input
range)
± 0.05%
Data for selecting a sensor
Input range (rated value)/input resistance
Current
4 mA to 20 mA/25 Ω
Permitted input current (destruction limit) Approx. 30 mA (limited electronically)
Load of the two-wire measuring transducer max. 750 Ω
Smoothing of the measured values Yes, can be assigned parameters in 4 steps
Step
None
Weak
Medium
Strong
Time constant
1 x cycle time
4 x cycle time
16 x cycle time
32 x cycle time

Table of Contents

Related product manuals