EasyManua.ls Logo

Siemens Simantic ET 200S - Page 202

Siemens Simantic ET 200S
274 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Analog electronic modules
4.14 2AI I 4WIRE High Speed analog electronic module (6ES7134-4GB61-0AB0)
ET 200S
4-72 Manual, Edition 10/2005, A5E00514527-01
Suppression of interference, limits of error
Crosstalk between the inputs > 50 dB
Operational limit
(in the entire temperature range, with
reference to the input range)
± 0.3 %
Basic error limit (operational limit
at 25 °C with reference to input range)
± 0.2 %
Temperature error (with reference to the
input range)
± 0.01 %/K
Linearity error (with reference to the input
range)
± 0.01 %
Repeatability
(in steady state at 25° C with reference to
input range)
± 0.05 %
Sensor power supply outputs
Number of outputs 2
Output voltage
With load
L+ (-2.5 V)
Output current
Rated value
Permitted range
90 mA (both channels)
0 mA to 90 mA
Short-circuit protection Yes, electronic
Data for selecting a sensor
Input range (rated value)/input resistance
Current
4 mA to 20 mA/50 Ω
0 mA to 20 mA/50 Ω
± 20 mA/50 Ω
Connection of the sensors
For current measurement as two-wire
transmitter
supported
Load of the two-wire measuring transducer max. 670 Ω
Maximum input current for current input
(destruction limit)
60 mA
Smoothing of the measured values Yes, can be assigned parameters in 4 steps by means
of digital filtering
Step
None
Weak
Medium
Strong
Time constant
1 x cycle time
64 x cycle time
128 x cycle time
512 x cycle time
1
Without encoder supply voltage
2
DPV1 only
3
Parameter assignment error
Violation of lower limit value
Violation of upper limit value
Open circuit (only with 4 mA to 20 mA)
Process interrupt lost

Table of Contents

Related product manuals