Analog electronic modules
4.14 2AI I 4WIRE High Speed analog electronic module (6ES7134-4GB61-0AB0)
ET 200S
4-72 Manual, Edition 10/2005, A5E00514527-01
Suppression of interference, limits of error
Crosstalk between the inputs > 50 dB
Operational limit
(in the entire temperature range, with
reference to the input range)
± 0.3 %
Basic error limit (operational limit
at 25 °C with reference to input range)
± 0.2 %
Temperature error (with reference to the
input range)
± 0.01 %/K
Linearity error (with reference to the input
range)
± 0.01 %
Repeatability
(in steady state at 25° C with reference to
input range)
± 0.05 %
Sensor power supply outputs
Number of outputs 2
Output voltage
• With load
L+ (-2.5 V)
Output current
• Rated value
• Permitted range
90 mA (both channels)
0 mA to 90 mA
Short-circuit protection Yes, electronic
Data for selecting a sensor
Input range (rated value)/input resistance
• Current
4 mA to 20 mA/50 Ω
0 mA to 20 mA/50 Ω
± 20 mA/50 Ω
Connection of the sensors
• For current measurement as two-wire
transmitter
supported
Load of the two-wire measuring transducer max. 670 Ω
Maximum input current for current input
(destruction limit)
60 mA
Smoothing of the measured values Yes, can be assigned parameters in 4 steps by means
of digital filtering
Step
None
Weak
Medium
Strong
Time constant
1 x cycle time
64 x cycle time
128 x cycle time
512 x cycle time
1
Without encoder supply voltage
2
DPV1 only
3
Parameter assignment error
Violation of lower limit value
Violation of upper limit value
Open circuit (only with 4 mA to 20 mA)
Process interrupt lost