EasyManua.ls Logo

Siemens Simantic ET 200S - Page 210

Siemens Simantic ET 200S
274 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Analog electronic modules
4.16 2AI RTD High Feature analog electronic module (6ES7134-4NB51-0AB0)
ET 200S
4-80 Manual, Edition 10/2005, A5E00514527-01
2AI RTD High Feature Technical Specifications (6ES7134-4NB51-0AB0)
Dimensions and Weight
Dimensions W × H × D (mm)
(the total dimensions depend on the
selected terminal module)
15 x 81 x 52
Weight Approx. 40 g
Data for specific modules
Supports isochronous operation no
Number of inputs 2
Cable length
Shielded
max. 200 m
Parameter length 7 bytes (4 bytes when used as 2AI RTD Standard)
Voltages, currents, potentials
Rated load voltage L+ (from the power
module)
24 VDC
Reverse polarity protection
Yes
Power supply of the transmitters Yes
Constant-current supply for
resistance-type sensors
Approx. 1.25 mA
Short-circuit protection
Yes
Galvanic isolation
Between the channels and backplane
bus
Yes
Between the channels and load
voltage L+
Yes
Between the channels
no
Permissible potential difference
Between M
ANA
and the central
grounding point (U
ISO
)
75 VDC / 60 VAC
Insulation tested 500 VDC
Current consumption
From load voltage L+
max. 30 mA
Power dissipation of the module Typically 0.6 W
Status, interrupts, diagnostics
Diagnostics function
Group error
Red "SF" LED
Diagnostic functions readable
Yes

Table of Contents

Related product manuals