Analog electronic modules
4.16 2AI RTD High Feature analog electronic module (6ES7134-4NB51-0AB0)
ET 200S
4-84 Manual, Edition 10/2005, A5E00514527-01
Assignment in the process input image (PII) in the case of SIMATIC S7
IB x
76 021345
000000
IB x + 1
76 021345
0
0000000
0: Measured resistance < response thresholdbetween prewarning threshold: 1
and response threshold
1: Measured resistance > response threshold
Assignment in the process input image (PII) in the case of SIMATIC S5
 

 
Measured resistance < response threshold
between prewarning threshold: 1
and response threshold
Measured resistance > response threshold
,%[
,%[
Notes on programming
Notice
Only the bits 0+2 or 3+5 are relevant for the purposes of evaluation in the process input
image. You can use bits 0+2 or 3+5 to monitor the temperature of a motor, for example.
Bits 0+2 or 3+5 in the process input image does not have a retentive function. Make sure
at parameter assignment that motor start-up is controlled (by means of an
acknowledgment), for example.
Bits 0+2 or 3+5 cannot be set at the same time, but set one after the other.
For safety reasons, always evaluate the diagnostic inputs of the 2AI RTD High Feature
because measurement is not possible when the EM is removed, when the power supply
to the EM has failed, or in the event of a wire break or short-circuit of the measuring lines.