EasyManua.ls Logo

Siemens Simantic ET 200S - Page 218

Siemens Simantic ET 200S
274 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Analog electronic modules
4.17 2AI TC Standard analog electronic module (6ES7134-4JB00-0AB0)
ET 200S
4-88 Manual, Edition 10/2005, A5E00514527-01
Insulation tested
500 VDC
Current consumption
From load voltage L+
max. 30 mA
Power dissipation of the module Typically 0.6 W
Status, interrupts, diagnostics
Diagnostics function
Group error
Red "SF" LED
Diagnostic functions readable
Yes
Analog value generation
Measuring principle Integrative
Integration time/conversion time/resolution
per channel:
Integration time can be assigned
parameters
Yes
Interference frequency suppression in
Hz
60 50
Integration time in milliseconds
16.7 20
Basic conversion time incl. integration
time in ms
55 65
Additional conversion time for wire
break check diagnosis in ms
20 20
Cycle time in ms
Number of active channels per module x conversion time
Resolution (including overrange)
15 bits plus sign
Suppression of interference, limits of error
Interference voltage suppression for
f = n x (f1 ± 1 %), (f1 = interference
frequency)
Common-mode interference (U
SS
)
Common mode interference
(peak value of interference < rated
value of input range)
min. 90 dB
min. 70 dB
Crosstalk between the inputs min. -50 dB
Operational limit (over the entire
temperature range, with reference to the
input range)
1
± 0.6 %
Basic error limit (operational limit at 25 °C
with reference to input range)
1
± 0.4 %
Temperature error (with reference to the
input range)
± 0.005 %/K
Linearity error (with reference to the input
range)
± 0.01 %
Repeatability
(in steady state at 25° C with reference to
input range)
± 0.05 %

Table of Contents