Analog electronic modules
4.21 2AO I Standard analog electronic module (6ES7135-4GB01-0AB0)
ET 200S
Manual, Edition 10/2005, A5E00514527-01
4-105
2AO I Standard Technical Specifications (6ES7135-4GB01-0AB0)
Dimensions and Weight
Dimensions W × H × D (mm)
(the total dimensions depend on the selected
terminal module)
15 x 81 x 52
Weight Approx. 40 g
Data for specific modules
Supports isochronous operation no
Number of outputs 2
Cable length
Shielded
max. 200 m
Parameter length 7 bytes
Voltages, currents, potentials
Rated load voltage L+ (from the power
module)
24 VDC
Reverse polarity protection
Yes
Galvanic isolation
Between the channels and backplane bus
Yes
Between the channels and load voltage
Yes
Between the channels
no
Permissible potential difference
Between MANA and the central grounding
point (U
iso
)
75 VDC / 60 VAC
Insulation tested 500 VDC
Current consumption
From the power supply L+
max. 150 mA
Power dissipation of the module max. 2 W
Status, interrupts, diagnostics
Diagnostics function
Group error
Red "SF" LED
Diagnostic functions readable
Yes
Analog value generation
Resolution (including overrange) ± 20 mA/13 bits + sign
4 mA to 20 mA/13 bits
Cycle time max. 1.5 ms
Settling time
For resistive load
0.1 ms
For capacitive load
0.5 ms
For inductive load
0.5 ms
Substitute values can be applied Yes