4 IQ-SENSE (6ES7138-4GA00-0AB0)
ET 200S
Manual, Edition 10/2005, A5E00514527-01
5-3
Parameters Range of values Default setting Applicability
Time value
• 5 ms
• 10 ms
• 20 ms
• 50 ms
• 100 ms
• 200 ms
• 500 ms
• 1 s
• 2 s
• 5 s
• 10 s
5 ms Channel
Teach-in disable
•
Teach-in
with button
possible
•
Teach-in
with button not
possible
Teach-in
with button
possible
Channel
Note
Unused channels of the module must be deactivated otherwise the wire break diagnosis will
be reported.
Measurement type parameter: De-activated
• All the diagnostics are suppressed.
• Sensitivity/distance values and circuit states are set to "0".
• The sensor is switched off.
5.2.2 Group diagnostics parameter
If group diagnostics is enabled, a pending diagnostics message is entered.
Reference
Information on channel-related diagnostics can be found in the
ET 200S Operating
Instructions
.
5.2.3 Synchronization group parameter
• Sensors between different modules of the 4 IQ-SENSE may influence one another (e.g.
scattered light).
• To prevent interference from neighboring sensors on different modules, this parameter
can be used to allocate a separate synchronization group to every module. Modules in
different synchronization groups do not interfere with one another.
• Sensors on the same module cannot interfere with one another.