Technical specifications
CPU 1517T-3 PN/DP (6ES7517-3TP00-0AB0)
42 Manual, 12/2017, A5E36285525-AB
Article number
6ES7517-3TP00-0AB0
Number of connectable IO Devices,
max.
512; In total, up to 1 000 distributed I/O devices
can be connected via AS-i, PROFIBUS or
PROFINET
Of which IO devices with IRT, max.
64
Number of connectable IO Devices for
RT, max.
512
of which in line, max.
512
Number of IO Devices that can be sim-
ultaneously activated/deactivated, max.
8; in total across all interfaces
Number of IO Devices per tool, max.
8
Updating times
The minimum value of the update time also
depends on communication share set for
PROFINET IO, on the number of IO devices, and
on the quantity of configured user data
Update time for IRT
for send cycle of 250 µs
250 µs to 4 ms
for send cycle of 500 µs
500 µs to 8 ms
for send cycle of 1 ms
1 ms to 16 ms
for send cycle of 2 ms
2 ms to 32 ms
for send cycle of 4 ms
4 ms to 64 ms
With IRT and parameterization of "odd"
send cycles
Update time = set "odd" send clock (any multiple
of 125 µs: 375 µs, 625 µs ... 3 875 µs)
Update time for RT
for send cycle of 250 µs
250 µs to 128 ms
for send cycle of 500 µs
500 µs to 256 ms
for send cycle of 1 ms
1 ms to 512 ms
for send cycle of 2 ms
2 ms to 512 ms
for send cycle of 4 ms
4 ms to 512 ms
PROFINET IO Device
Services
PG/OP communication
Yes
S7 routing
Yes
Isochronous mode
No
Open IE communication
Yes
IRT
Yes
MRP
Yes
MRPD
Yes; Requirement: IRT
PROFIenergy
Yes
Shared device
Yes

Related product manuals