Article number 6DL1131-6DF00-0EK0
General information
Firmware version V1.0
• FW update possible
Yes
Usable terminal block TB type K0
Color code for module-specic color identica‐
tion plate
CC42
Engineering with
• SPPA-T3000 can be congured/integrated
from version
V8.0
Operating mode
• DI
Yes
Redundancy
• Redundancy capability
No
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Input current
Current consumption (rated value) 16 mA
Current consumption, max. 20 mA
Power loss
Power loss, typ. 3.75 W
Address area
Address space per module
• Address space per module, max.
14 byte; Without SOE: PII: 1 byte, +1 byte for QI
information, +1 byte of PROFINET status data; PIO:
1 byte of PROFINET status data; with SOE: PII: 1
byte, +1 byte for QI information, +10 bytes for SOE,
+1 bytes of PROFINET status data; PIO: 1 byte PRO‐
FINET status data
Digital inputs
Input characteristic curve in accordance with IEC
61131, type 1
Yes
Input characteristic curve in accordance with IEC
61131, type 3
Yes
Time stamping Yes; Resolution 10 ms
Time stamp (with precision of 1 ms) Yes; Resolution 1ms
Input voltage
• for signal "0"
-125 ... +5 V
• for signal "1"
+11 ... +125 V
Encoder
Connectable encoders
Technical specications
DI 8x24...125VDC HA
30 Equipment Manual, 10/2021, A5E39288633-AD