EasyManua.ls Logo

Siemens SIMATIC 6DL1131-6DF00-0PK0 - Page 23

Siemens SIMATIC 6DL1131-6DF00-0PK0
38 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Article number 6DL1131-6DF00-0PK0
between the channels and backplane bus
Yes
Permissible potential difference
between different circuits 250 V AC/300 V DC
Isolation
Isolation tested with 3 500 V DC/1 min, type test
Ambient conditions
Ambient temperature during operation
horizontal installation, min.
-40 °C
horizontal installation, max.
70 °C
vertical installation, min.
-40 °C
vertical installation, max.
60 °C
Dimensions
Width 22.5 mm
Height 115 mm
Depth 138 mm
Weights
Weight, approx. 165 g
Cycle time
The cycle time describes the period of time in which the signals from the inputs are acquired
and processed.
Operating mode Cycle time
of ongoing operation 150 μs
with time stamping 1 ms (100 μs for time stamps)
Minimum pulse length
In order for a pulse or an edge transition to be reliably detected by the I/O module, the signal
status must be active for at least for the time period of the minimum pulse length.
The minimum pulse length is greater than the input delay and greater than the cycle time.
Technical specifications
Digital input module DI 8x24...125VDC HA (6DL1131-6DF00-0PK0)
Manual, 11/2017, A5E39288633-AB 23

Other manuals for Siemens SIMATIC 6DL1131-6DF00-0PK0

Related product manuals