A.2 Parameter assignment [ID: 80184760203]
Parameter assignment in the user program
You can reconfigure individual channels of the module in RUN without this having an effect
on the other channels.
Changing parameters in RUN
The "WRREC" instruction is used to transfer the parameters to the module using data
record 128. The parameters set in STEP 7 are not changed in the CPU, which means that the
parameters set in STEP 7 will be valid again after a restart.
Output parameter STATUS
If errors occur when transferring parameters with the "WRREC" instruction, the module
continues operation with the previous parameter assignment. The STATUS output parameter
contains a corresponding error code.
The STATUS output parameter is 4 bytes long and is configured as followed:
● Byte1: Function_Num, general error code
● Byte2: Error_Decode, location of the error code
● Byte3: Error_Code_1, error code
● Byte4: Error_Code_2, manufacturer-specific extension of the error code
Module-specific errors are displayed via Error_Decode = 0x80 and Error_Code_1 /
Error_Code_2.
Error_
Code_
1
Error_
Code_
2
Cause Solution
0xB0 0x00 Number of the data record unknown Enter valid number for data record.
0xB1 0x01 Length of the data record is incorrect Enter valid value for data record length.
0xB2 Varia‐
ble
Module cannot be reached
● Check station - is the module plugged in
correctly?
● Check the parameters of the WRREC
instruction.
0xE0 0x01 Wrong version in the header Correct the version number of the parameter block.
0xE0 0x02 Header error (number or length of parameter block) Correct the length and number of the parameter
blocks.
0xE1 0x01 Reserved bit set Check and correct the parameters
0xE1 0x02 Invalid diagnostics enable bit set for operating mode
0xE1 0x03 Invalid hardware interrupt enable bit set for operating
mode
0xE1 0x07 Invalid coding for input delay
0xE1 0x0E Invalid redundancy parameter assignment
Drivers, parameters, diagnostics messages and address space
A.2 Parameter assignment
Digital input module DI 8x24...125VDC HA (6DL1131-6DF00-0PK0)