A.4 Diagnostics messages and maintenance events [ID: 91008185867]
Diagnostics messages
A diagnostics message is generated for every fault identified. The DIAG LED on the module
flashes.
There is additionally a channel-specific display of the diagnostics through the corresponding
channel fault LEDs
The diagnostic messages can, for example, be read from the diagnostic buffer of the CPU.
Diagnostic messages are either assigned to an input for specific channels or assigned to all
inputs as a module alarm. For diagnostic messages which affect the entire module, all channels
are switched off. For diagnostic messages which refer to individual channels, only the
corresponding digital input is affected.
Table A-1 Diagnostics messages, their meaning and how to deal with them
Diagnostics mes‐
sage
Error
code
Assignment Meaning Solution
Wire break 6
H
Digital input Impedance of encoder circuitry is too
high
Use a different encoder type or
modify the wiring, for example,
using cables with a larger cross-
section
Wire break between the module and
sensor
Connect the cable
Channel not connected (open)
● Disable diagnostics
● Connect encoder contacts
with a 25 kΩ to 45 kΩ resistor.
Parameter as‐
signment error
10
H
Module
● Parameter assignment does not
match the terminal block used
● Incorrect parameter assignment
● Correct the parameter
assignment
● Check terminal block
1
Supply voltage
missing
11
H
Module Missing or insufficient supply voltage
L+
● Check wiring of the supply
voltage L+ on the terminal
block
● Check the terminal block type
Channel/compo‐
nent temporarily
unavailable
1F
H
Module Update of the firmware is being per‐
formed or has been canceled.
The module does not import any
process values during this time.
● Restart firmware update
● Wait for firmware update
Hardware inter‐
rupt lost
16
H
Module Error is reported because the events
occur faster than they can be pro‐
cessed in the system
Module is faulty 100
H
Module Internal module error has occurred Replace I/O module
Drivers, parameters, diagnostics messages and address space
A.4 Diagnostics messages and maintenance events
Digital input module DI 8x24...125VDC HA (6DL1131-6DF00-0PK0)
32 Manual, 11/2017, A5E39288633-AB