Diagnostics alarms
5.2 Diagnostics alarms
Communication module CM 4xIO-Link 4xM12(6ES7147-5JD00-0BA0)
Manual, 10/2017, A5E32352322-AE
27
LEDs Qn
Valid for IO-Link port in SIO mode.
Table 5- 4 Status displays of the Q1, Q2, Q3, and Q4 LEDs
Q1, Q2, Q3, and Q4 LEDs
Meaning
Off
Process signal = 0 in SIO mode, deactivated or in IO-Link mode
On
Process signal = 1 in SIO mode
5.2
Diagnostics alarms
For each diagnostic event, a diagnostics alarm is issued and the DIAG LED flashes red on
the communication module. You can read out the diagnostics alarms, for example, in the
diagnostics buffer of the CPU. You can evaluate the error codes with the user program.
Table 5- 5 Error types
Diagnostics
alarm
Error
code
Meaning (IO-Link error code)
IO-Link
master
IO-Link
device
Short-circuit 1
H
Short-circuit at the process cables on the IO-Link device (1804
H
)
X
Short-circuit on IO device (7710
H
)
X
Undervoltage 2
H
Supply voltage too low (5111
H
, 5112
H
)
X
Overvoltage 3
H
Supply voltage too high (5110
H
)
X
Overtemperature 5
H
Temperature exceeded on master (1805
H
)
X
Temperature exceeded on device (4000
H
, 4210
H
)
X
Wire break 6
H
No IO-Link device connected
There is a break on the signal line to the IO-Link device
IO-Link device cannot communicate due to a different error
(1800
H
)
X
Overflow 7
H
Process tag range exceeded (8C10
H
)
Measuring range exceeded (8C20
H
)
X
Underflow 8
H
Process tag range too low (8C30
H
)
X
Error 9
H
All IO-Link error codes which are not listed here are mapped to
this PROFIBUS DP error
X