Interrupts/diagnostics alarms
5.3 Alarms
Communication module CM 8x IO-Link + DI 4x24VDC M12-L (6ES7148-6JG00-0BB0
32 Equipment Manual, 09/2020, A5E49284833-AA
5.3 Alarms
The IO-Link master can generate diagnostic alarms of the type (severity) "Diagnostics" or
"Maintenance" on behalf of the IO-Link device or the IO-Link port.
Alarms of the "Diagnostics" type indicate a malfunction of the IO-Link device / port and
should be corrected immediately.
Alarms of the "Maintenance" type indicate a maintenance demand. The aim is to detect
and eliminate potential faults at an early stage, even before functionality is impaired.
Process alarm events signal the corresponding process states on the IO-Link device (e.g.
limit exceeded)
5.3.1 Diagnostics alarms
IO-Link master error types
All IO-Link events of the type Error generated by the IO-Link device or port are mapped to the
PROFINET diagnostics alarm of the type (severity) "Diagnosis" of the assigned submodule.
IO-Link device diagnostics
The IO-Link master generates PROFINET channel diagnostics (CET, ECET) from the IO-Link
events of an IO-Link device according to the following mapping regulations:
In the "IO-Link Device Diagnostics - Page 1" (CET 0x9500
H) the IO-Link event codes in the
range 0x0000 - 0x7FFF
H are displayed directly:
ECET
H = IO-Link Event CodeH
In the "IO-Link Device Diagnostics - Page 2" (CET 0x9501
H) the IO-Link event codes in the
range 0x8000 - 0xFFFF
H are displayed directly:
ECET
H = (IO-Link Event CodeH0x8000H)
Table 5- 5 Overview of error types IO-Link device diagnostics
IO-Link event
code
Error type
(CET)
Extended error
type (ECET)
Error text Meaning
0x0000 -
0x7FFFH
0x9500
H
(38144D)
0x0000 - 0x7FFF
H
(0 - 32767D)
Error /
warning
See the manual of the IO-Link de-
vice or IODD file used.
0x8000 -
0xFFFFH
0x9501
H
(38134D)
0x0000 - 0x7FFF
H
(0 - 32767D)
Error /
warning
See the manual of the IO-Link de-
vice or IODD file used.
Example of displaying the IO-Link event codes:
An IO-Link device generates event code 0x4000
H (type "Error").
The channel diagnostics from the event code:
PROFINET channel diagnostics type: Diagnosis, CET: 0x9500
H, ECET: 0x4000H
Diagnostics alarm "IO-Link Device Diagnostics - Page 1, Temperature fault - Overload",
generated from the IO-Link event code 0x4000
H.
IO-Link port diagnostics