Technical data
12.5 Electromagnetic compatibility of the converters
SIMATIC ET 200pro FC-2 converter
226 Operating Instructions, 04/2015, FW V4.7.3, A5E34257324B AB
12.5.4.1
ET 200pro FC-2 frequency converter in a drive system in accordance with EN 61800-3
Explanatory notes for EN 61800-3+A11
The EN 61800-3+A11 product standard for "Adjustable speed electrical power drive
systems, Part 3: EMC requirements and specific test methods" specifies limit values for
noise radiation and interference immunity. The EMC product standard EN 61800-3+A11
does not apply directly to a frequency converter but to a complete drive system, which
comprises the complete circuitry, motor and cables in addition to the converter.
Limit values for compliance with EN 61800-3 Category C3
The following table lists the key limit values for compliance with EN 61800-3 on devices with
restricted availability
for a drive system in accordance with Category C3 (Category C3: Drive
system (PDS) with a rated voltage of < 1000 V. For use in a second environment), i.e.,
use
in second environment
(industrial) with commissioning and installation carried out by an
EMC expert.
Table 12- 6 Limit values for noise radiation for a drive system compliant with Category C3
EMC phenomena
Basic standard
for test proce-
dures
Limit value
Radiated emissions
EN 55011
Class A, Group 1
Conducted emissions
EN 55011
Class A, Group 2
Table 12- 7 Limit values for interference immunity for a drive system compliant with Category C3
EMC phenomena
Basic standard
for test proce-
dures
Level
Evaluation crite-
rion
Voltage dips EN 61800-3-A11
30 %, 10 ms 1)
B
60 %, 100 ms 1) C
95 %, 5 s 2)
C
Voltage interruptions EN 61800-3-A11
100 %, 230 ms 2)
C
100 %, 120 ms (regenerative feed-
back) 3)
C
Harmonics at rated load
5.
7.
11.
13.
--
Motor operation
EN 61800-3-A11
18,4%
15,6%
8,8%
8,4%
Regenerative
feedback
EN 61800-3-A11 20,3% 18,4% 9,8% 9,3%
Electrostatic discharge
EN 61000-4-2
8 kV, air discharge (housing)
B
Interference pulses
Burst
EN 61000-4-4
2 kV/5 kHz (electric power cable)
B
Voltage surge EN 61000-4-5 2 kV, phase – ground (electric power
cable)
B
1 kV, phase – phase (electric power
cable)
B