CM 1xDALI command list
3.2 Control gear dimming
ET 200SP CM 1xDALI Communication Model Description
Programming Manual, 12/2019, A5E47581955-AA
23
3.2.2 Set level
Description
Use this CM command to set the target arc power level of control gears.
Command ID
2
Input Param-
eters
Byte 0
0 (16#00) to 63 (16#3F): short address
128 (16#80) to 143 (16#8F): group address
253 (16#FD): unaddressed devices
255 (16#FF): all the control gears
Byte 1 Level actions
16#00: OFF
16#01: UP
16#02: DOWN
16#03: STEP UP
16#04: STEP DOWN
16#05: RECALL MAX LEVEL
16#06: RECALL MIN LEVEL
16#07: STEP DOWN AND OFF
16#08: ON AND STEP UP
16#0A: GOTO LAST ACTIVE LEVEL
16#FF: Direct Arc Power Control (DAPC)
Byte 2
If Byte 1 is 16#FF (DAPC), Byte 2 is the target level to set.
If Byte 1 is not 16#FF, the CM 1xDALI ignores value of this byte.
Response
Parameters
Byte 0 Return code (Page 51)
3.2.3 Query control gear color
Description
Use this CM command to query the current color of a type 8 control gear (color con-
trol device).
Command ID
3
Input Param-
eters
Byte 0 Short address
Response
Parameters
Byte 0
Return code (Page 51)
Byte 1 Shows the color type
16#10: color xy-coordinate
16#20: color temperature
Others value: color type is unknown.
If the control gear type is not device type 8 (color control), this byte
shows 0.