CM 1xDALI command list
3.2 Control gear dimming
ET 200SP CM 1xDALI Communication Model Description
24 Programming Manual, 12/2019, A5E47581955-AA
Byte 2 to 3 Shows the value of the color type
Color coordinate-x (when Byte 1 is 16#10)
Color temperature (when Byte 1 is 16#20)
Unknow color type (when Byte 1 is 16#00)
Byte 4 to 5 Shows the value of the color type
Color coordinate-y (When Byte 1 is 16#10)
Color type is not color-coordinate. (when Byte 1 is 16#00)
3.2.4 Set control gear color
Description
Use this CM command to set the color of type 8 control gears (color control device).
Command ID
4
Input Param-
eters
Byte 0
0 (16#00) to 63 (16#3F): short address
128 (16#80) to 143 (16#8F): group number
253 (16#FD): unaddressed devices
255 (16#FF): all devices
Byte 1 Sets the color type
16#10: color coordinate-xy
16#20: color-temperature
Others value: color-type is unknown.
If the control gear type is not device type 8 (color control), this byte
shows 0.
Byte 2 to 3 Sets the value of color type
Color coordinate-x (when Byte 1 is 16#10)
Color temperature (when Byte 1 is 16#20)
Byte 4 to 5 Sets the value of color type
Color coordinate-y (when Byte 1 is16#10.)
Color type is not color-coordinate. (When Byte 1 is 16#00)
Response
Parameters
Byte 0 Return code (Page 51)