CM 1xDALI command list
3.3 Diagnostic
ET 200SP CM 1xDALI Communication Model Description
Programming Manual, 12/2019, A5E47581955-AA
27
1
Example
For the control gear whose short address is 5, if you want to check whether the bit 1 of
basic control gear status is set to 1, you should set the input parameter
s as:
16#00
16#00 16#00 16#00 16#00 16#00 16#02 16#00 16#00
16#00 16#00 16#00 16#00 16#00 16#0
0 16#00 16#00
16#00 16#00 16#00 16#00 16#00 16#00 16#00 16#00
16#00 16#00 16#00 16#00 16#00 16#00 16#00 16#00
16#00 16#00 16#00 16#00 16#00 16#00 16#00 16#00
16#0
0 16#00 16#00 16#00 16#00 16#00 16#00 16#00
16#00 16#00 16#00 16#00 16#00 16#00 16#00 16#00
16
#00 16#00 16#00 16#00 16#00 16#00 16#00 16#00
If the bit 1 of basic control gear status is set to 1, you will get the response parameters as:
16#00
16#20 16#00 16#00 16#00 16#00 16#00 16#00 16#00
2
For the description about each bit of basic control gea
r and type-related failure status,
refer to the following two tables.
Table 3- 1 Basic control gear status
Bit
Status
Explanation
Bit 0 Control gear
failure
The control gear cannot be operated as intended.
Bit 1
Lamp failure
The lamp cannot operate as intended.
Bit 2
Lamp on
The lamp is on.
Bit 3 Limit error The last requested target level is modified in accordance with limitations of "minimum level"
or "maximum level".
Bit 4
Fade running
The fade timer is running.
Bit 5
Reset state
All the parameters of this device are at their reset value.
Bit 6
No short address
No short address is assigned to this device.
Bit 7
Power cycle seen
An external power cycle occurred.