CM 1xDALI command list
3.4 Configuration
ET 200SP CM 1xDALI Communication Model Description
Programming Manual, 12/2019, A5E47581955-AA
41
3.4.12 Remove control gear scene
Description
Use this CM command to remove the scene configuration of a control gear.
This command has the same behavior as calling "Set control gear scene (Page 40)"
when scene level is 255 (16#FF).
Command ID
32
Input Param-
eters
Byte 0
Short address of the control gear
Byte 1
Scene number
Response
Parameters
Byte 0 Return code (Page 51)
3.4.13 Start download control gear parameters
Description
Use this CM command to send the parameters saved in the CM 1xDALI to the physi-
cal device.
The CM 1xDALI provides a response to the CPU when the procedure is started. You
can check the progress and result of the procedure by "querying the current com-
mand progress (Page 49)".
Command ID
33
Input Param-
eters
Byte 0 Short address of the device
Response
Parameters
Byte 0 Return code (Page 51)
3.4.14 Start upload control gear parameters
Description
Use this CM command to query the parameters of the physical device, and save them
in CM 1xDALI.
The CM 1xDALI sends a response to the CPU when it starts the procedure. You can
check the progress and result of the procedure by "querying the current command
progress (Page 49)".
Command ID
34
Input Param-
eters
Byte 0 Short address
Response
Parameters
Byte 0 Return code (Page 51)