CM 1xDALI command list
3.6 Progress
ET 200SP CM 1xDALI Communication Model Description
50 Programming Manual, 12/2019, A5E47581955-AA
Comments
If no procedure has started, Byte 1 and Byte 2 of the response parameters are 255 (16#FF).
Progress Byte 2 of CM command 33 Start download control gear parameters": (Page 41)
Progress number
Device progress
16#01
Querying status of the control gear
16#02
Setting basic parameters
16#03
Setting type-related parameters
16#04 Setting group configuration
16#05
Setting scene configuration
Progress Byte 2 of CM command 34 Start upload control gear parameters: (Page 41)
Progress number
Device progress
16#01
Querying basic parameters
16#02
Querying extended parameters
16#03
Querying group configuration
16#04
Querying scene configuration
16#05
Saving all parameters
Progress Byte 2 of CM command 41 Start download input device parameters: (Page 45)
Progress number
Device progress
16#11
Querying status of the input device
16#12
Setting parameters of the input device
16#13~16#32
Setting parameters of the input device instances
Progress Byte 2 of CM command 42 Start upload input device parameters: (Page 41)
Progress number
Device progress
16#01
Querying input device parameters and saving
16#02~16#21
Querying input device instances parameters and saving
Progress Byte 2 of CM command 51 Start scan and assign short address: (Page 46)
Progress number
Device progress
16#01 to 16#40:
Scan in progress, increase by 1 for each device scanned.
16#41:
Assigning short address
16#42:
Querying device status