CM 1xDALI command list
3.7 Return code and control status
ET 200SP CM 1xDALI Communication Model Description
Programming Manual, 12/2019, A5E47581955-AA
51
3.6.2 Cancel current command
Use this CM command to stop current running CM command.
Byte 0 The value is 0.
Byte 0 Return code (Page 51)
3.7 Return code and control status
3.7.1 Return code
The command has completed successfully.
16#01 The procedure has started successfully. You can check the progress by the
command Query current command progress (Page 49).
The CM 1xDALI is busy with the last command.
Timeout: the procedure did not complete within a limit time.
The procedure is canceled.
16#85 The CM 1xDALI received an error response frame after sending the query
command. The error might be caused by a short address conflict or a DALI
device failure.
Note: Not every short address conflict can be detected. It can only be detected
when the conflicted devices send the response frame at the same time.
Not supported: the action is not supported by the CM 1xDALI.
No data: there is no data saved in CM 1xDALI or no response on the DALI bus.
Status error: the CM 1xDALI is not in the normal state.
16#8B Configuration mismatch. The physical device doesn't match the control gear or
input device adding by the "Add control gear (Page 32)" instruction or "Add input
device (Page 42)" instruction.
16#8C The short address is not configured. No device with this short address exists on
No device is configured with this short address.
No physical device with the specified short address is on the DALI bus.
The scan procedure has stopped abnormally.
The CM 1xDALI cannot send commands to the DALI bus.
16#91 The device type of the control gear specified in the CM command "Set control
gear extended parameters (Page 37)" or input device specified in the CM com-
mand "Set instance parameters of input device (Page 45)" does not match the