CM 1xDALI command list
3.7 Return code and control status
ET 200SP CM 1xDALI Communication Model Description
Programming Manual, 12/2019, A5E47581955-AA
51
3.6.2 Cancel current command
Description
Use this CM command to stop current running CM command.
Command ID
57
Input Param-
eters
Byte 0 The value is 0.
Response
Parameters
Byte 0 Return code (Page 51)
3.7 Return code and control status
3.7.1 Return code
Error code
Description
16#00
The command has completed successfully.
16#01 The procedure has started successfully. You can check the progress by the
command Query current command progress (Page 49).
16#82
The CM 1xDALI is busy with the last command.
16#83
Timeout: the procedure did not complete within a limit time.
16#84
The procedure is canceled.
16#85 The CM 1xDALI received an error response frame after sending the query
command. The error might be caused by a short address conflict or a DALI
device failure.
Note: Not every short address conflict can be detected. It can only be detected
when the conflicted devices send the response frame at the same time.
16#87
Not supported: the action is not supported by the CM 1xDALI.
16#88
Invalid input parameters
16#89
No data: there is no data saved in CM 1xDALI or no response on the DALI bus.
16#8A
Status error: the CM 1xDALI is not in the normal state.
16#8B Configuration mismatch. The physical device doesn't match the control gear or
input device adding by the "Add control gear (Page 32)" instruction or "Add input
device (Page 42)" instruction.
16#8C The short address is not configured. No device with this short address exists on
the DALI bus.
16#8D
No device is configured with this short address.
16#8E
No physical device with the specified short address is on the DALI bus.
16#8F
The scan procedure has stopped abnormally.
16#90
The CM 1xDALI cannot send commands to the DALI bus.
16#91 The device type of the control gear specified in the CM command "Set control
gear extended parameters (Page 37)" or input device specified in the CM com-
mand "Set instance parameters of input device (Page 45)" does not match the
physical device.