Programming
5.3 System function blocks
ET 200SP Communication module CM 1xDALI (6ES7137-6CA00-0BU0)
Manual, 06/2019, A5E46959434-AA
27
The FB receives and reports the event messages which are sent be the DALI-2 input
devices.
When Bit 1 or Bit 2 of the CM_STATUS show "1", all the other DALI function blocks
cannot be executed. You can choose any of the following actions to resume the status of
CM 1xDALI.
Set the input CM_RESET to 1.
Send the DALI command "STOP QUIESCENT MODE" or "ENABLE APPLICATION
CONTROLLER" (refer to IEC 62386-103) to the CM 1xDALI through other DALI
application controllers.
A defined set of messages and their content are shown at the inputs EVENT_MSG,
EVENT_SCHEME, EVENT_SRC_1, EVENT_SRC_2 and EVENT_INFO.
Other generic event messages are shown at the outputs RSV_MSG, RSV_MSG_LEN
and RSV_MSG_VAL. The content is shown without interpretation at the output
RSV_MSG_VAL.
Parameter
The following table shows the parameters of the function block.
Parameter
Decla-
ration
Data
type
Memory
area
Description
HW_ID Input HW_IO I, Q, M,
D, L or
Constant
The hardware identifier of the CM 1xDALI
CM_RES
ET
BOOL I, Q, M,
D, L or
Constant
Stop quiescent mode and re-enable the DALI application controller upon a
raising edge. After this action, Bit 1 and Bit 2 of the CM_STATUS will be
reset to 0.
CONN_E
RR
Output
BOOL I, Q, M,
D, L
The status of CPU communication with CM 1xDALI:
CONN_ERR = 0: No error when the CPU communicates with CM
1xDALI.
CONN_ERR = 1: Error occurs when the CPU communicates with CM
1xDALI.
CM_STAT
US
DWORD I, Q, M,
D, L
Indicate the status of the CM 1xDALI:
16#00000000: The status of the CM 1xDALI is OK.
For the detailed explanation for each Bit of the CM_STATUS, refer to the
following section "Parameter CM_STATUS".
EVENT_M
SG
BOOL I, Q, M,
D, L
The status of the sensor event. When the CM 1xDALI receives a sensor
event, the EVENT_MSG remains true for one cycle:
EVENT_MSG = 0: No sensor event
EVENT_MSG = 1: A sensor event is received.