Programming
5.6 Diagnostic function blocks
ET 200SP Communication module CM 1xDALI (6ES7137-6CA00-0BU0)
Manual, 06/2019, A5E46959434-AA
55
Parameter
Declaration
Data type
Memory
area
Description
EXT_ST
ATUS
1
BYTE Show the type-related failure status of the control gear which com-
pliant with the IEC62386-20x.
When 1 ≤ ACTUAL_TYPE ≤ 8, each Bit of EXT_STATUS indicates
the different error types. Otherwise, the value of EXT_STATUS is 0.
ACTUAL
_LEVEL
USInt The actual level of the control gear.
1
For the detailed description about each bit of Control Gear EXT_STATUS, refer to the following table.
Bit
Type 1
(emergency)
Type 2 (dis-
charge)
Type 3 (hal-
ogen)
Type 4 (in-
candescent)
Type 5
(converter)
Type 6
(LED)
Type 7
(switch)
Type 8 (col-
or control)
0 Circuit failure
Mains volt-
age too low
Short circuit Load over-
current shut-
down
Output fault
detected
Short circuit Load error XY-
coordinate
color point
out of range
1 Battery dura-
tion failure
Mains volt-
age too high
Open circuit Open circuit Reserved Open cir-
cuit
Error detec-
tion in hold
off
Color tem-
perature out
of range
2 Battery fail-
ure
Converter
thermal
overload
Load de-
crease
Load de-
crease
Load de-
crease
Last thresh-
old acted
upon
‘00’ up
switch-on
’01’ up
switch-off
‘10’ down
switch on
‘11’ down
switch off
Auto calibra-
tion running
3 Emergency
lamp failure
Reserved Load in-
crease
Load in-
crease
Load in-
crease
Auto calibra-
tion success-
ful
4 Function test
max delay
exceeded
Ignition time
out
Current
protector
active
Reserved Current
protector
active
Reserved Color type
XY-
coordinate
active
5 Duration test
max delay
exceeded
Reserved Thermal
shutdown
Thermal
shutdown
Thermal
shutdown
Color type
color tem-
perature
active
6 Function test
failed
Lamp volt-
age out of
spec
Thermal
overload
Thermal
overload
Thermal
overload
Color type
primary N
active
7 Duration test
failed
Lamp cycling
failure
Reference
measure-
ment failed
Reference
measure-
ment failed
Reference
measure-
ment failed
Reference
measure-
ment failed
Color type
RGBWAF
active

Table of Contents