Programming
5.7 Configuration function blocks
ET 200SP Communication module CM 1xDALI (6ES7137-6CA00-0BU0)
Manual, 06/2019, A5E46959434-AA
75
5.7.5
DALI_ECG_QUERY_EXT_PARAM
Description
DALI_ECG_QUERY_EXT_PARAM
is used for querying the extended parameters of DALI
control gears.
When you set the input "PHY_DEV" to 1, this function block queries the extended
parameters from the physical device (refer to data flow path 6 (Page 23)).
When you set the input "PHY_DEV" to 0, this function block queries the parameters which
are saved in CM 1xDALI (refer to data flow path 2 (Page 23)).
The extended parameters have the following features:
The extended parameters are type-related.
The extended parameters in the physical device can only be queried from the control
gears whose type range is from 1 to 8; Otherwise, the error code “16#87” (Not supported)
is shown in the output parameter of STATUS.
The extended parameters which are saved in CM 1xDALI can only be queried from the
control gear whose type is 1, or 4 to 8.
You can set the extended parameters of control gear by using
DALI_ECG_SET_EXT_PARAM (Page 79).