Programming
5.7 Configuration function blocks
ET 200SP Communication module CM 1xDALI (6ES7137-6CA00-0BU0)
94 Manual, 06/2019, A5E46959434-AA
The following table shows the parameters of the function block:
SET Input
BOOL I, Q, M, D,
L or Con-
Set device parameters of the sensor upon a rising edge.
ADDRES
S
USInt I, Q, M, D,
L or Con-
Specify the short address of the device.
Range: 0 to 63
OPER_M
BYTE I, Q, M, D,
Operating mode of the sensor device which is defined by the device
PWR_CY
CLE
BOOL I, Q, M, D,
L
Power cycle notification flag.
PWR_CYCLE = 1: After completing its external power cycle, the sen-
sor generates a power cycle event message.
CM_DALI InOut "DALI_CT
The data block of
specifies the CM 1xDALI which com-
municates with the current function block.
BUSY Output BOOL I, Q, M, D,
L
Status parameter:
• BUSY = 0: Processing of job is terminated.
• BUSY = 1: Job is still being committed.
ACTIVE BOOL I, Q, M, D,
L
Status parameter:
• ACTIVE = 0: Job is not yet started.
• ACTIVE = 1: Job is being executed.
DONE BOOL I, Q, M, D,
L
Status parameter:
• DONE = 0: Job is not yet started or still executing.
• DONE = 1: Job is executed without errors.
ERROR BOOL I, Q, M, D,
L
Status parameter:
• ERROR = 0: No error occurs.
• ERROR = 1: Error occurs during processing.
STATUS BYTE I, Q, M, D,
L
When ERROR = 0, STATUS has
following three values:
• 16#00: Idle
• 16#01: Executing
• 16#7F: Completed
When ERROR = 1, STATUS
shows the detailed error code. For
the detailed meaning of each
error code, refer to Parameter
STATUS (Page 106).