Article number 6DL1134-6UD00-0PK0
Address space per module, max.
9 byte; 8 bytes for inputs and 1 byte for QI infor‐
mation
Address space per module with HART, max.
29 byte; 8 bytes for inputs, 1 byte for QI informa‐
tion, 20 bytes for HART information
Address space per module with MultiHART,
max.
16 byte; 8 bytes for inputs, 1 byte for QI informa‐
tion, 6 bytes for HART information, 1 byte for HART
command
Analog inputs
Number of analog inputs 4
For current measurement
4
permissible input current for current input (de‐
struction limit), max.
24 mA
Input ranges (rated values), currents
0 to 20 mA
Yes; 16 bit incl. sign
Input resistance (0 to 20 mA)
250 Ω
4 mA to 20 mA
Yes; 16 bit incl. sign
Input resistance (4 mA to 20 mA)
250 Ω
Cable length
shielded, max.
800 m; with unshielded cables up to 800 m, re‐
member that (external) EMC loads can cause incor‐
rect measured values
Analog value generation for the inputs
Integration and conversion time/resolution per
channel
Resolution with overrange (bit including
sign), max.
16 bit; 14 bit at 60 Hz (0 ... 10 mA), 16 bit at 10 Hz,
15 bit at 50 Hz and 15 bit at 60 Hz interference
suppression
Smoothing of measured values
parameterizable
Yes; none, weak, medium, strong, channel-by-
channel
Encoder
Connection of signal encoders
for current measurement as 2-wire transduc‐
er
Yes
Errors/accuracies
Linearity error (relative to input range), (+/-) 0.01 %
Temperature error (relative to input range), (+/-) 0.005 %/K
Crosstalk between the inputs, min. 60 dB
Repeat accuracy in steady state at 25 °C (relative
to input range), (+/-)
0.05 %
Operational error limit in overall temperature
range
Current, relative to input range, (+/-)
0.5 %
Basic error limit (operational limit at 25 °C)
Current, relative to input range, (+/-)
0.1 %
Interrupts/diagnostics/status information
Technical speci󹪝cations
8.1 Technical speci󹪝cations
AI 4xI 2-/4-wire HART ISOL HA
Equipment Manual, 07/2022, A5E50101523-AB 53