Cause Remedy
0xE1 0x01 Reserved bit set Check and correct the parameters
0xE1 0x02 Invalid diagnostics enable bit set for operating mode
0xE1 0x04 Invalid value for hardware interrupt limit
0xE1 0x08 Invalid coding for interference frequency suppres‐
sion / integration time
0xE1 0x09 Invalid coding for smoothing
0xE1 0x10 Invalid measurement type
0xE1 0x11 Invalid measuring range
0xE1 0x13 Incompatible terminal block
0xE1 0x20 Incorrect call length or incorrect DS number
0xE1 0x21 Incorrect number of HART repetitions
Valid parameters
Only the values speci󹪝ed in the following are permitted. Values that are not listed are rejected
by the I/O module.
Each parameter data record is checked by the I/O module. If a parameter with errors is detected,
the complete data record is rejected and the parameters of the I/O module remain unchanged.
A.2 Parameter assignment and structure of the module/channel
parameters
Structure of data record 128
Data record 128 has a length of 68 bytes.
It contains module parameters and technology parameters of the 4 channels.
The channel and technology parameters are divided into parameters that in󹪞uence the actual
analog value acquisition, diagnostics enables and basic parameters of the HART communication.
You can specify and change other parameters or HART-speci󹪝c settings with data records 131 to
134. See section HART-speci󹪝c settings (Page 82).
Parameters, diagnostics messages and address space
A.2 Parameter assignment and structure of the module/channel parameters
AI 4xI 2-/4-wire HART ISOL HA
58 Equipment Manual, 07/2022, A5E50101523-AB