There is additionally a channel-specic display of the diagnostics through the corresponding
channel fault/channel status LEDs.
The diagnostics messages can, for example, be read out in the diagnostics buer of the CPU.
Diagnostic messages are assigned either to one input on a channel-specic basis or to all inputs
as a module message. In the event of diagnostics messages that aect the entire module, all
channels are switched o. For diagnostics messages that relate to individual channels, only the
corresponding analog input is aected.
Table A-1 Diagnostic messages, their meaning and possible remedies
Diagnostics mes‐
sage
Error
code
Assignment Meaning Remedy
Channel/compo‐
nent temporarily
unavailable
1F
H
Module Update of the rmware is being performed or
has been canceled. The module does not
perform any measurements during this time.
• Restart rmware update
• Wait for rmware update
Wire break 6
H
Analog input
• Impedance of encoder circuitry is too
high
• Wire break between the module and sen‐
sor
• Channel not connected (open)
• Use a dierent encoder
type or modify the wiring,
for example, using cables
with a larger cross-section
• Connect the cable
• Disable diagnostics
• Connect the encoder con‐
tacts
High limit violated 7
H
Analog input
• The analog value is above the overrange.
• Short-circuit of input to L+
Correct the module/encoder
tuning
Low limit violated 8
H
Analog input The analog value is below the underrange. Correct the module/encoder
tuning
Parameter assign‐
ment error
10
H
Module
• Parameter assignment does not match
the terminal block used
• Incorrect parameter assignment
• Correct the parameter as‐
signment
• Check terminal block
1
Supply voltage
missing
11
H
Module Missing or insucient supply voltage L+
• Check wiring of the supply
voltage L+ on the terminal
block
• Check the terminal block
type
Hardware inter‐
rupt lost
16
H
Module Error is reported because the events occur
faster than they can be processed in the sys‐
tem
Module is faulty 100
H
Module Internal module error has occurred Replace module
Short-circuit to
ground
106
H
Analog input Short-circuit of the analog input to transduc‐
er supply or M
Correct the process wiring
Short-circuit/over‐
load at external
encoder supply
10E
H
Analog input
• Short-circuit of the encoder supply to
ground
• Encoder supply overload
• Correct the module/encod‐
er tuning
• Check the wiring
Parameters, diagnostics messages and address space
A.4 Diagnostics alarms
AI 4xI 2-/4-wire HART ISOL HA
64 Equipment Manual, 07/2022, A5E50101523-AB