IB x + 7 6 5 4 3 2 1 0
0…1 Analog value, analog input 0
:
:
:
:
6…7 Analog value, analog input 3
8 - - - - QAI3 QAI2 QAI1 QAI0
9
HART range
:
:
HART range
When HART variables or the multiHART area is used, the HART area is arranged directly 󹪞ush
against the QI bits of the analog inputs.
The structure of the HART area is dependent on the con󹪝guration:
In the con󹪝guration with 4 HART variables in the input area, the area has a length of 20 bytes
and always contains 4 HART variables, each with a 4-byte value and a 1-byte quality code
(QC).
IB x + HART range
9
:
12
Value Con󹪝gured HART variable 1
13 QC
14
:
17
Value Con󹪝gured HART variable 2
18 QC
19
:
22
Value Con󹪝gured HART variable 3
23 QC
24
:
27
Value Con󹪝gured HART variable 4
28 QC
In the con󹪝guration with 1 multiHART area in the input/output area, the area has a length of
6 bytes:
IB x + HART range
9 Acknowledgment multiHART range
10
:
13
Value HART variable
14 QC
Parameters, diagnostics messages and address space
A.7 Address space
AI 4xI 2-/4-wire HART ISOL HA
Equipment Manual, 07/2022, A5E50101523-AB 69