HART proto‐
col error dur‐
ing re‐
sponse
Meaning Explanation
6 Query rejected 0: Unspeci󹪝ed
1: Compact format not supported
2: SHC not supported
3: Impermissible command
4: No resources
5: Channel in standby mode
1
6…127: Reserved
128...255: Manufacturer-speci󹪝c
7 Pro󹪝le query rejected 0: Not speci󹪝ed (not supported)
8 Manufacturer-speci󹪝c query
rejected
0: Not speci󹪝ed (not supported)
1
An external HART request has been rejected because the channel is not the active channel of a
redundancy pair. The request must be sent to the connected 󹪝eld device via the partner module.
Example of HART programming (HART command interface)
For HART channel 0, command 01 is to be sent in transparent message format to the HART 󹪝eld
device with address "98 CF 38 84 F0".
A positive edge at input 4.0 of a digital input module leads to the writing of the HART command.
The following assumptions are made:
The module address of the I/O module is 512 (200
H
).
The data record is stored in DB80: starting from address 0.0, length of 11 bytes.
In this example, DB80 (request data record for channel 0) consists of 11 bytes.
Explanation
A I 4.0
FP M 101.0
= M 104.0
m2: CALL SFB53, DB53
REQ :=M104.0 Write request
ID :=DW#16#200
INDEX :=80
Module address
Data record number 80
LEN :=11 Length 11 bytes
DONE :=M51.7
BUSY :=M51.0
ERROR :=M51.6
STATUS :=MD92
RECORD :=P#DB80.DBX0.0 BYTE 11
A M 51.0
SPB m2
BE
Block status or error information
Source area in DB80
HART operating data records
B.2 HART job and response data records
AI 4xI 2-/4-wire HART ISOL HA
78 Equipment Manual, 07/2022, A5E50101523-AB