VALID :=M49.7
BUSY :=M49.1
ERROR :=M49.6
STATUS :=MD100
LEN :=MW104
RECORD :=P#DB81.DBX0.0 BYTE 200
A M 49.1
SPB m3
BE
Block status or error information
Target area in DB81
The program part A M 49.1 to SPB m3 is only required if reading is to occur within a block cycle.
As long as the processing status (byte 0 of DB81) is at 3 (waiting, executing), the response has
not yet been received from the eld device. As soon as the processing status changes to greater
than 3, the HART request is nished.
With a processing status of 4, the request nished without errors and the response data can be
evaluated.
With a processing status of 5, the request also nished without errors but without response data
from the eld device.
With a processing status of 6 or 7, the request nished with errors. You can nd more detailed
information in byte 1 of DB81 (see table "HART group fault display") and for a HART protocol error
also in byte 2 of DB81 (see table "HART protocol error during response").
B.3 HART directory
Structure of the HART directory
Byte Meaning Comment
0 Prole Revision Number = 2, 0 (Revision 2.0)
1
2 Index of Client Management = 255 (not relevant)
3 Number of Clients = 1
4 Number of Channels = 4
5 Write Read Index Oset = 1 (The response to a job data record is
made with the data record number of the
request data record + 1)
6 Index of HMD Feature Parameter = 149
7 Index of HMD Module Parameter = 255 (not relevant)
8 Start Index of Burst Buer Area = 255 (not relevant)
9+n Index of HMD Channel Parameter (Channel
n)
= 131+n
9+n+4 Index of HART Client Channel Message Data = 80+(2*n)
The HART request data records cannot be
congured. Data sets starting from data set
number 80 (80, 82, 84, 86) are always used.
HART operating data records
B.3 HART directory
AI 4xI 2-/4-wire HART ISOL HA
80 Equipment Manual, 07/2022, A5E50101523-AB