EasyManua.ls Logo

Siemens SIMATIC ET 200SP HA - Page 41

Siemens SIMATIC ET 200SP HA
114 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
WARNING
Cabling
You must use shielded cables to ensure installation free of interference voltage.
(FAIW-005)
Parameter assignment
Set the following parameters for the corresponding channel:
Parameter Channel with internal sensor supply
Measurement type Current (2-wire transmitter)
Measuring range 4 to 20 mA
Behavior after channel fault Passivate the channel / passivate the entire module
Interference frequency suppression 50 Hz / 60 Hz
HART gate On / O󹪜
Diagnostics, Wire break Activated / deactivated
Smoothing 1 / 4 / 16 / 64
HART enabled Activated / deactivated
Number HART message frame repetitions 0 to 10
Diagnostics HART Activated / deactivated
Applications of the F-I/O module
6.2 Application case 1: SIL3/Cat.3/PLd, 2-wire transmitter, 1oo1
F-AI 8xI 2-/4-wire HART HA
Equipment Manual, 09/2021, A5E50557845-AA 41

Table of Contents

Other manuals for Siemens SIMATIC ET 200SP HA

Related product manuals