WARNING
Requirement for sensor
To achieve SIL3/Cat.3/PLd using this wiring, you must use a quali󹪝ed sensor.
(FAIW-004)
WARNING
Cabling
You must use shielded cables to ensure installation free of interference voltage.
(FAIW-005)
Parameter assignment
Set the following parameters for the corresponding channel:
Parameter Channel with internal sensor supply
Measurement type Current (2-wire transmitter)
Measuring range 4 to 20 mA
Behavior after channel fault Passivate the channel / passivate the entire module
Interference frequency suppression 50 Hz / 60 Hz
HART gate On / O󹪜
Diagnostics, Wire break Activated / deactivated
Smoothing 1 / 4 / 16 / 64
HART enabled Activated / deactivated
Number HART message frame repetitions 0 to 10
Diagnostics HART Activated / deactivated
Applications of the F-I/O module
6.3 Application case 1a: SIL3/Cat.3/PLd, 2-wire transmitter, 1oo1 (high availability)
F-AI 8xI 2-/4-wire HART HA
Equipment Manual, 09/2021, A5E50557845-AA 43