SIMATIC ET200SP PS
Manual, 03.2018, A5E43207434
39
6EP7133-6AB00-0BN0 (24 V/5 A)
6EP7133-6AE00-0BN0 (24 V/10 A)
Ambient temperature
• Remark
-30 … 70 °C for natural convection (self convection)
Derating at ≤ 60 °C:
85 V AC and 170 V AC: 90 % P
out rated
≥ 100 V AC and ≥ 200 V AC: 100 % P
out rated
between 85 V AC and 100 V AC, 170 V AC and 200 V AC linear interpolation
at > 60 °C: Additionally, 3 % I
out rated
/K
Tested according to:
• EN 60068-2-1 cold
• EN 60068-2-2 dry heat
• EN 60068-2-78 humid heat, constant
• EN 60068-2-14 temperature change
Transport and storage temperature -40 … 70 °C
Tests (packed for shipping) according to:
• EN 60068-2-1 cold
• EN 60068-2-2 dry heat
• EN 60068-2-30 humid heat, cyclic
Climatic class 3K3 acc. to EN 60721, 5 - 95 % without condensation
Mechanical stressing during operation Tested according to:
• EN 60068-2-6, test FC
3.5 mm deflection in the range of 5 - 8.4 Hz
2 g acceleration in the range of 8.4 - 150 Hz
• EN 60068-2-27 shock, test Ea:
acceleration 150 m/s
2
, test duration 11 ms
Damaging gases Tested according to:
• EN 60068-2-42 sulfur dioxide
• EN 60068-2-43 hydrogen sulfide
Atmospheric pressure Operation:
• 1080 - 795 hPa (-1000 - 2000 m)
• Overvoltage category:
II to 2000 m (EN 60950-1)
Storage:
• 1080 - 660 hPa (-1000 - 3500 m)