Troubleshooting
11-10
FM 353 Stepper Drive Positioning Module
6ES7 353-1AH01-8BG0
Table 11-4 Diagnostic interrupt, continued
Message/
Display
Error message,
error analysis and remedy
Byte.
Bit
0.1 Internal errors Error response: “Everything Off”, as in Table 11-2
2.4
Internal module power supply failure
SF
(8034)
Cause S Drastic voltage dip
S FM 353 power supply faulty
DC5V
DIAG
Effect Deactivate entire FM 353
Elimination S Check FM 353 power connection
S If FM 353 power supply defective, replace FM 353
3.2
FEPROM errors
SF
(8042)
Cause Memory for firmware code faulty
DC5V
DIA
Effect
Elimination Replace the FM 353
3.3
RAM errors
(8043)
Cause S Faulty RAM data memory
S Faulty flash-EPROM data memory
Effect
Elimination Replace the FM 353
3.6
Process interrupt lost
(8046)
Cause S A process interrupt event was detected by the FM 353 and can-
not be reported, because the same event has not yet been ac-
knowledged by the user program/CPU.
S Faults on backplane bus
Effect
Elimination S Incorporate OB40 into user program
S Check bus connection of the module
S Deactivate using MD5 process interrupt
0.2 External errors Error response: “Everything Off”, as in Table 11-2
0.6
Module not parameterized
SF
(8006)
Cause No MPI parameterization data received from the CPU
DC5V
DIAG
Effect MPI interface is initialized with default values. MPI address = 12
Elimination Check parameterization, see S7-300 description
Note: (xxxx) value = Hexadecimal notation in diagnostic buffer