EasyManua.ls Logo

Siemens SIMATIC FM 353 - Page 324

Siemens SIMATIC FM 353
361 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting
11-22
FM 353 Stepper Drive Positioning Module
6ES7 353-1AH01-8BG0
Table 11-8 General data errors, machine data errors, traversing program errors, continued
Cl.
Mes-
sage/
Display
Error message,
error analysis and remedy
No.
General data errors Error response: “Warning” see Table 11-2
4 (04) 11 (0B) Set actual value, actual value incorrect CBS
Cause Actual value falls outside the software limit switches or out-
side
the range 10
9
MSR
or
DB
Effect Set actual value does not become effective
Elimination Input a correct value
4 (04) 12 (0C) Set reference point value, reference point incorrect CBS
Cause Value falls outside the range 10
9
MSR
or
Effect Set reference point does not become effective
DB
Elimination Input a correct value
4(04) 13 (0D) Digital output not possible CBS
Cause Output not available for direct output of the user program
or
Effect Output is not executed
DB
Elimination S Correct user program
S Correct parameterization of the output assignment within
the MD35 to the desired assignment
4(04) 14 (0E) Request application data incorrect CBS
Cause Incorrect request code
or
Effect Old application data are retained
DB
Elimination Request code 0-6, 16-23 and 25 possible
4(04) 15 (0F) Teach In, program number incorrect CBS
Cause The program was not parameterized or read in.
or
Effect Teach In is not executed
DB
Elimination Parameterize and read in program or correct program num-
ber
4(04) 16 (10) Teach In, block number incorrect CBS
Cause The block number in the program selected is not in place.
or
Effect Teach In is not executed
DB
Elimination Specify correct block number
4(04) 17 (11) Teach In, dwell time or subprogram request in block CBS
Cause The block number in the program selected is not in place or
incorrect block number was selected.
or
DB
Effect Teach In is not executed
Elimination Specify correct block number
Cl. = Detail event class, No. = Detail event number, CBS = checkback signals, DB = data block