Mounting and connecting the device
3.1 Preparing for installation
Unified Comfort Panels
32 Operating Instructions, 03/2020, A5E46641217-AA
3.1.4 Checking clearances
The following clearances are required around the HMI device to ensure sufficient self-
ventilation:
At least 15 mm to both the right and left of the mounting cutout (in x direction) to allow for
insertion of the mounting clips during installation
At least 50 mm above and 50 mm below the mounting cutout (in the y direction) for
ventilation
At least 10 mm behind the rear panel of the HMI device (in the z direction)
The following figure shows the clearances for mounting the HMI devices in landscape format
and portrait format using MTP1900 Unified Comfort as an example:
Clearance for mounting in landscape format
Clearance for mounting in portrait format
x
At least 15 mm distance
y
At least 50 mm distance
z
At least 10 mm distance
Note
Ensure that the maximum ambient temperature is not exceeded when mounting the device
in a cabinet and especially in a closed enclosure.