3.4.6 Connecting a USB device
Below are examples of industrial grade devices you can connect to the USB type A
interfaces of the HMI device:
External mouse
External keyboard
Printer
USB stick
Industrial USB Hub 4, article number 6AV6671-3AH00-0AX0
Mobile handheld reader ("Barcode Scanner"), article number 6GF3320-0HT01 or
6GF3340-0HT01
Note
USB cable length maximum 1.5 m
USB cables with lengths of more than 1.5
m do not ensure secure data transfer.
The cable may not
be longer than 1.5 m.
USB devices with a separate power supply
If you connect an external device with a 230 V power supply to the USB port in a plant that is
electrically isolated, you might
experience functional problems.
Use a non
-isolated plant installation.
Excessive rated load of the USB interface
A USB device with too high a power load may possibly
cause functional problems.
Observe the values for the maximum load rating of the USB interface, see section
"
Technical specifications (Page 156)".
Potential loss of data
I
f the HMI device accesses its data when a USB storage medium is removed, the data on
the storage medium cannot be fully read or written, or it may even be destroyed.
If your process requires you to change the USB storage medium duri
ng operation, you need
t
o take this into account by employing suitable mechanisms in the configuration.
Do not remove the USB storage medium during operation while data is being accessed.