SIMATIC PN/J1939 LINK
Operating Instructions, 12/2018, A5E45307564-AA
63
Technical specifications
12
12.1
Technical specifications of the PN/J1939 LINK
Technical specifications of PN/J1939 LINK
Article number
6BK1623-0AA00-0AA0
General information
Product type designation PN/J1939 LINK
Firmware version
V1.0
FW update possible
Yes
Vendor identification (VendorID) 0x002A
Product function
I&M data
Yes
Isochronous mode
No
Installation type/mounting
Mounting DIN rail, wall mounting, portrait mounting
Mounting position Any
Recommended mounting position Horizontal
Supply voltage
Type of supply voltage 24 V DC
Rated value (DC) 24 V
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Overvoltage protection Yes
Short-circuit protection Yes
Mains buffering
Mains/voltage failure stored energy time
10 ms; PN side
Input current
Current consumption (rated value) 0.09 A
Current consumption, max. 0.11 A
Power loss
Power loss, typ. 2.2 W
Engineering with
STEP 7 V14 SP1
STEP 7 TIA Portal configurable/integrated
as of version