5-22
ET 200U Distributed I/O Station
EWA 4NEB 812 6087–02b
Setting switch 8 results in different conditions:
Table 5-8 Function of Switch 8
Order No. Function
318–8MB12 DP Standard: Bus protocol to PROFIBUS–DP draft stan-
dard (can be used as from COM ET 200 version 4.0). The
slow mode must be set in a bit of the parameterization
frame ( Figure 5-5, Section 5.1.1)
DP Siemens: Bus protocol to DP Siemens. The
ET 200U automatically switches into the slow mode when it
identfies an IP 265.
318–8MC11 DP Standard: Bus parameters in accordance with
PROFIBUS–DP (from COM ET 200, V 4.0). Slow mode
must be set by means of a bit in the parameterization frame
( Figure 5-5, Section 5.1.1).
FMS–Norm: Bus parameters in accordance with FMS stan-
dard. Slow mode must be set by means of a bit in the para-
meterization frame ( Figure 5-5, Section 5.1.1).
The permissible parameter values are listed in Table 6-3 in
Section 6.1.
Set station number 52 and DP Standard:
Press switch (position “ON”)
4
Positional value:
+16
+32
52
1
2
3
4
5
6
7
8
DP StandardDP Siemens
Setting Switch 8
Example of an
“318–8MB12
ET 200U(DP Standard): AddressAssignm.,Starting–Up, DiagnosingFaultsUsing COM ET 200