6-13
ET 200U Distributed I/O Station
EWA 4NEB 812 6087–02b
6.3.2 Object List (OV)
The FMS services “Read” and “Write” can be used by the FMS master to
access objects defined in the object list (OV).
The ET 200U(DP Standard/FMS) always generates the full object list, even
in a mixed configuration or as a combi–slave.
The individual objects of the ET 200U(DP Standard/FMS) are addressed via
an index in the static object list. The following table illustrates how the ob-
ject list of the ET 200U(DP Standard/FMS) is structured.
Table 6-6 Structure of the Object List of the ET 200U(DP Standard/FMS)
Meaning Designation Index
(Decimal)
Input
Index
(Decimal)
Output
Slot 0 Input / Output 30 31
Slot 1 Input / Output 32 33
Slot 2 Input / Output 34 35
Slot 3 Input / Output 36 37
Slot 4 Input / Output 38 39
Slot 5 Input / Output 40 41
Slot 6 Input / Output 42 43
Slot 7 Input / Output 44 45
...
Slot 31 Input/Ouput 92 93
Diagnostics data Diagnostics data – 110
Parameter data Parameter data – 120
DP inputs DP Input – 130
FMS inputs FMS Input – 140
DP outputs DP Output – 150
FMS outputs FMS Output – 160
Diagnostics event
(with FMS service
“Event Notifica-
tion)
Diagnost. event – 170
The index of the slot of an I/O module can be calculated as follows:
Index of an input slot
= (Slot 2) + 30
Index of an output slot = (Slot 2) + 31
Static Object List
ET 200U(DP Standard/FMS): Modes, Settings and Comm. Capabilities of IM 318–C