6-15
ET 200U Distributed I/O Station
EWA 4NEB 812 6087–02b
Table 6-9 Coding the I/O Modules in an ET 200U(DP Standard/FMS)
Order No. of
Module
Type Length Access
Mode
1
Object-
Code
2
Delay
(ms)
3
Current
Con-
sumption
(mA)
Power
Loss
(W)
Digital input modules 6ES5 ...:
420–8MA11 unsigned8 1 R 7 2.5 to 5 16 4.5
421–8MA12 unsigned8 1 R 7 2.3 to 4.5 34 4.5
422–8MA11 unsigned16
*
2
*
R 7 3 to 4 50 4.5
430–8MB11 unsigned8 1 R 7 1.4 to 5 5 2
430–8MC11 unsigned8 1 R 7 10 to 20 16 2.8
430–8MD11 unsigned8 1 R 7 10 to 20 16 2.5
431–8MA11 unsigned8 1 R 7 4 to 5.5 32 2
431–8MC11 unsigned8 1 R 7 10 to 20 32 2.5
431–8MD11 unsigned8 1 R 7 10 to 20 32 3.6
433–8MA11 unsigned8 1 R 7 1 to 10 6 2.4
437–8EA12 unsigned8 1 R 7 40 50 0.45
Digital output modules 6ES5 ...:
440–8MA11 unsigned8 1 R/W 7 < 1 15 3
440–8MA21 unsigned8 1 R/W 7 < 1 15 4.8
441–8MA11 unsigned8 1 R/W 7 < 1 14 3.5
450–8MB11 unsigned8 1 R/W 7 < 1 15 5
450–8MD11 unsigned8 1 R/W 7 < 1 14 3.5
451–8MA11 unsigned8 1 R/W 7 < 1 24 4
451–8MD11 unsigned8 1 R/W 7 < 1 25 3.5
451–8MR11 unsigned8 1 R/W 7 < 1 30 1.6
451–8MR12 unsigned8 1 R/W 7 < 1 30 1.6
452–8MR11 unsigned8 1 R/W 7 < 1 14 2
453–8MA11 unsigned8 1 R/W 7 < 1 20 1
457–8EA12 unsigned8 1 R/W 7 < 1 55 0.5
* Since this module has both inputs and outputs, an “input” and an “output” object are generated.
1 Meanings of abbreviations: R = Read (read access) und W = Write (write access).
2 Meanings of the abbreviations: 7 = Simple–Variable, 8 = Array. The FMS master can access an array element via a
subindex.
3 In input modules, the delay is the time elapsing between a change of the input signal and the change of the I/O bus
status. In output modules, the delay is the time elapsing between the change of the I/O bus signal and the resulting