EasyManua.ls Logo

Siemens SIMATIC S5 ET 200U - Analog Input Module 464-8 ME11, 4 4 to 20 Ma (Absolute Value); Analog Input Modules 464-8 MC11, -8 MD11 (Bipolar Fixed-Point Number)

Siemens SIMATIC S5 ET 200U
383 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7-18
ET 200U Distributed I/O Station
EWA 4NEB 812 6087–02b
Table 7-6 Analog Input Modules 464–8MC11, –8MD11 (Bipolar Fixed–Point Number)
Units
Measured Value in mV
High Byte Low Byte Range
in V
in mA
> 4095 20.000 40.0 0 1 1 1 1 1 1 1 1 1 1 1 1 0 0 1 Overflow
4095 19.995 39.9902 0 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 Overrange
2049 10.0048 20.0098 0 100000000001000
2048 10.000 20.0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0
1024 5.000 10.0 0 010000000000000
1 0.0048 0.0098 0 000000000001000
0 0.0 0.0 0 000000000 0 0 0 0 0 0 Nominal Range
–1 –0.0048 –0.0098 1 111111111111000
–1024 – 5.000 –10.0 1 110000000000000
–2048 –10.000 –20.0 1 100000000000000
–2049 –10.0048 –20.0098 1 0 1 1 1 1 1 1 1 1 1 1 1 0 0 0 Overrange
–4095 –19.995 – 39.9902 1 000000000001000
<–4095 –20.000 –40.0 1 0 0 0 0 0 0 0 0 0 0 0 1 0 0 1 Overflow
464–8MC11 (4 "10 V)
464–8MD11 (4 "20 mA)
Table 7-7 Analog Input Module 464–8ME11, 4 4 to 20 mA (Absolute Value)
Units Measured Value in mA High Byte Low Byte Range
> 4095 > 32.769 0 1 1 1 1 1 1 1 1 1 1 1 1 0 0 1 Overflow
4095
2561
31.992
20.008
0
0
1
1
1
0
1
1
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
1
0
0
0
0
0
0
Overrange
2560 20.0 0 1 0 1 0 0 0 0 0 0 0 0 0 0 0 0
2048 16.0 0 100000000 0 0 0 0 0 0 Nominal Range
512 4.0 0 001000000000000
511 3.992 0 0 0 0 1 1 1 1 1 1 1 1 1 0 0 0
Td
384 3.0 0 000110000000000
Transducer
Failure?
0 0.0 0 000000000000000
F
a
il
ure
?
–1 –0.008 1 111111111111000
< –4095 <–32.769 1 0 0 0 0 0 0 0 0 0 0 0 1 0 0 1
Analog Value Processing

Table of Contents

Related product manuals