7-22
ET 200U Distributed I/O Station
EWA 4NEB 812 6087–02b
Table 7-12 Analog Input Module 464–8MA21, 4  50 mV with Linearization and with Temperature Com-
pensation (Bipolar); Thermoelement Type L (Iron/Copper–Nickel (Konstantan), according to 43710)
Units Thermo
Voltage
in mV*
Tempera-
ture in °C
High Byte Low Byte Range
1361 0 0 1 0 1 0 1 0 1 0 0 0 1 0 0 1 Overflow
901 901 0 0 0 1 1 1 0 0 0 0 1 0 1 0 0 1 Overrange**
900 53.14 900 0 0 0 1 1 1 0 0 0 0 1 0 0 0 0 0
500 27.85 500 0 000111110100000
250 13.75 250 0 000011111010000
100 +5.37 100 0 000001100100000
1 0.05 1 0 000000000001000
0 0 0 0000000000 0 0 0 0 0 0 Nominal Range
–1 –0.05 –1 1 111111111111000
–100 –4.75 –100 1 111110011100000
–150 –6.60 –150 1 111101101010000
–190 –7.86 –190 1 111101000010000
–199 –8.12 –199 1 111100111001000
–200 –200 1 1 1 1 1 0 0 1 1 1 0 0 0 0 0 1 Overrange**
–273 1 1 1 1 0 1 1 1 0 1 1 1 1 0 0 1 Overflow
X X X X X X X X X X X X X X X 0 1 0 Wire Break
This value corresponds to the terminal temperature at wire break
* For a reference temperature of 0 °C (32 °F)
** In the overrange, the current slope of the characteristic curve is maintained when leaving the linearized nominal range.
Analog Value Processing

Table of Contents