8-11
ET 200U Distributed I/O Station
EWA 4NEB 812 6087–02b
Technical Specifications
Input voltage V
input
Permissible range, continu-
ously
Frequency
Inrush current
120 V / 230 V AC
(selectable)
93 V to 132 V / 187 V
to 264 V AC
47 Hz to 63 Hz
< 24 A
Efficiency under rated condi-
tions
82 %
Output voltage V
output
Rated output voltage
Tolerance
Residual ripple
Switching surges (at 30
MHz)
24 V DC
" 5 %
100 mV
ss
500 mV
ss
Output current I
output
Rated output current 10 A
Short–circuit protection Electronic
Current limiting
Threshold value
approx. 1.1 I
AN
Overvoltage protection –
Voltage response
Dynamic at load change
(10 to 90 %)
Correction time
5 %
3 ms
Bridging of line voltage drops 10 ms (at 230 V)
Permissible ambient tempera-
ture
Self–ventilation during
operation
During storage/shipping
0 °C to 60 °C
–25 °C to 85 °C
Humidity class to DIN 40 040 F
Safety class I
Degree of protection (DIN 40
050, IEC 144)
IP 20
Electrical isolation
Test voltage, primary/se-
condary
To VDE 0160,
VDE 0805
3.75 kV AC eff.,
UL 508,
File E 143289
RI specification to VDE 0871 Class A
Design Snap–on housing
Dimensions (W x H x D) mm 190 126 135
Connection
Cross–section
Via screw–type termi-
nals
1.5 mm
2
, stranded
2.5 mm
2
, solid
Sensor line No
Powerfail signal No
Weight approx. 2.5 kg
(5.5 lbs.)
Note
The performance data specified are referred to vertical installation of the
module. Horizontal installation is possible for ambient temperatures
< 40 °C and if the power output is reduced to 24 V / 6 A.