8-59
ET 200U Distributed I/O Station
EWA 4NEB 812 6087–02b
8.10 Analog Output Modules
Analog Output Module 2 "10 V (6ES5 470–8MA12)
pr93a049
Technical Specifications
Address ID for ET 200U
S DP Siemens
S DP Standard
2AQ or 021
2AQ or 097
Output range
(rated values)
"10 V
Number of outputs 2
Galvanic isolation yes (outputs to
grounding point and
between outputs)
Input resistance w3.3 k
Capacitive load incl. cable
capacitance
<100 nF
Connection method two– or four–wire
connection
Digital representation of output
signal
11 bits + sign (1024
units = rated value)
Measured value representation two’s complement
(left–justified)
Conversion time
(0 to 100 %)
max. 0.15 ms
Permissible overload 25 %
Short–circuit protection yes
Short–circuit current "30 mA
Permissible voltage difference
to ground and between outputs
max. 75 V DC/
60 V AC
Basic error limits
(operational error limit at
25 _C, referred to input ranges
of module)
"0.3 %
Operational error limits
(0 to 60 _C, referred to input
ranges of modue)
"0.6 %