Technology instructions
10.3 Motion control
S7-1200 Programmable controller
System Manual, V4.2, 09/2016, A5E02486680-AK
789
Parameter of position monitoring is faulty. Invalid value in <Axis
name>.PositioningMonitoring.ToleranceTime
16#0030 Value has an incorrect number format or is
outside the valid number range
• Download error-free configuration to the con-
troller; enable the axis again with instruction
"MC_Power".
• Correct the incorrect value online;
acknowledge error with instruction "MC_Reset"
and restart the command, if necessary.
Inconsistent PROFIBUS parameterization; the sum of Ti and To is greater than one DP cycle
16#0030 Value has an incorrect number format or is
outside the valid number range
Download error-
free configuration to the controller;
enable the axis again with instruction
Parameter of standstill monitoring is faulty. Invalid value in <Axis
name>.StandStillSignal.MinDwellTime
16#0030 Value has an incorrect number format or is
outside the valid number range
• Download error-free configuration to the con-
troller; enable the axis again with instruction
"MC_Power".
• Correct the incorrect value online;
acknowledge error with instruction "MC_Reset"
and restart the command, if necessary.
Parameter of following error monitoring is faulty. Invalid value in <Axis
name>.FollowingError.MinValue
16#0030 Value has an incorrect number format or is
outside the valid number range
• Download error-free configuration to the con-
troller; enable the axis again with instruction
"MC_Power".
• Correct the incorrect value online;
acknowledge error with instruction "MC_Reset"
and restart the command, if necessary.
Invalid value for the configuration date <Axis name>.Modulo.Length
16#0030 Value has an incorrect number format or is
outside the valid number range
• Download error-free configuration to the con-
troller; enable the axis again with instruction
"MC_Power".
• Correct the incorrect value online;
acknowledge error with instruction "MC_Reset"
and restart the command, if necessary.
Invalid value for the configuration date <Axis name>.Modulo.StartValue
16#0030 Value has an incorrect number format or is
outside the valid number range
• Download error-free configuration to the con-
troller; enable the axis again with instruction
"MC_Power".
• Correct the incorrect value online;
acknowledge error with instruction "MC_Reset"
and restart the command, if necessary.