EasyManua.ls Logo

Siemens SIMATIC S7-1200 - Page 790

Siemens SIMATIC S7-1200
1614 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technology instructions
10.3 Motion control
S7-1200 Programmable controller
790 System Manual, V4.2, 09/2016, A5E02486680-AK
ErrorID
ErrorInfo
Description
Remedy
16#8630
Invalid value for the configuration date <Axis name>.Actor.DriveParameter.ReferenceSpeed
16#0030 Value has an incorrect number format or is
outside the valid number range
Download error-free configuration to the con-
troller; enable the axis again with instruction
"MC_Power".
Correct the incorrect value online;
acknowledge error with instruction "MC_Reset"
and restart the command, if necessary.
16#8631
The set fine resolution for Gn_XIST2 is invalid. Invalid value in <Axis
name>.Sensor.Sensor[1].Parameter.FineResolutionXist2
16#0030 Value has an incorrect number format or is
outside the valid number range
Download error-free configuration to the con-
troller; enable the axis again with instruction
"MC_Power".
Correct the incorrect value online;
acknowledge error with instruction "MC_Reset"
and restart the command, if necessary.
16#8632
The number of determinable encoder revolutions is invalid. Invalid value in <Axis
name>.Sensor.Sensor[1].Parameter.DeterminableRevolutions
16#0030 Value has an incorrect number format or is
outside the valid number range
Download error-free configuration to the con-
troller; enable the axis again with instruction
"MC_Power".
Correct the incorrect value online;
acknowledge error with instruction "MC_Reset"
and restart the command, if necessary.
16#8633
The specified approach direction of the homing switch for passive homing is invalid. Invalid value in
<Axis name>.Sensor.Sensor[1].PassiveHoming.Direction
16#8634
Parameter of the following error monitoring is faulty. Invalid value in <Axis
name>.FollowingError.MaxValue
16#0030 Value has an incorrect number format or is
outside the valid number range
Download error-free configuration to the con-
troller; enable the axis again with instruction
"MC_Power".
Correct the incorrect value online;
acknowledge error with instruction "MC_Reset"
and restart the command, if necessary.
16#8635
Parameter of the following error monitoring is faulty. Invalid value in <Axis
name>.FollowingError.MinVelocity
16#0030 Value has an incorrect number format or is
outside the valid number range
Download error-free configuration to the con-
troller; enable the axis again with instruction
"MC_Power".
Correct the incorrect value online;
acknowledge error with instruction "MC_Reset"
and restart the command, if necessary.