Technology instructions
10.3 Motion control
S7-1200 Programmable controller
790 System Manual, V4.2, 09/2016, A5E02486680-AK
Invalid value for the configuration date <Axis name>.Actor.DriveParameter.ReferenceSpeed
16#0030 Value has an incorrect number format or is
outside the valid number range
• Download error-free configuration to the con-
troller; enable the axis again with instruction
"MC_Power".
• Correct the incorrect value online;
acknowledge error with instruction "MC_Reset"
and restart the command, if necessary.
The set fine resolution for Gn_XIST2 is invalid. Invalid value in <Axis
name>.Sensor.Sensor[1].Parameter.FineResolutionXist2
16#0030 Value has an incorrect number format or is
outside the valid number range
• Download error-free configuration to the con-
troller; enable the axis again with instruction
"MC_Power".
• Correct the incorrect value online;
acknowledge error with instruction "MC_Reset"
and restart the command, if necessary.
The number of determinable encoder revolutions is invalid. Invalid value in <Axis
name>.Sensor.Sensor[1].Parameter.DeterminableRevolutions
16#0030 Value has an incorrect number format or is
outside the valid number range
• Download error-free configuration to the con-
troller; enable the axis again with instruction
"MC_Power".
• Correct the incorrect value online;
acknowledge error with instruction "MC_Reset"
and restart the command, if necessary.
The specified approach direction of the homing switch for passive homing is invalid. Invalid value in
<Axis name>.Sensor.Sensor[1].PassiveHoming.Direction
Parameter of the following error monitoring is faulty. Invalid value in <Axis
name>.FollowingError.MaxValue
16#0030 Value has an incorrect number format or is
outside the valid number range
• Download error-free configuration to the con-
troller; enable the axis again with instruction
"MC_Power".
• Correct the incorrect value online;
acknowledge error with instruction "MC_Reset"
and restart the command, if necessary.
Parameter of the following error monitoring is faulty. Invalid value in <Axis
name>.FollowingError.MinVelocity
16#0030 Value has an incorrect number format or is
outside the valid number range
• Download error-free configuration to the con-
troller; enable the axis again with instruction
"MC_Power".
• Correct the incorrect value online;
acknowledge error with instruction "MC_Reset"
and restart the command, if necessary.