Commissioning
12.4 Operating and system states
S7-1500R/H redundant system
System Manual, 01/2024, A5E41814787-AF
407
RUN-Solo → SYNCUP, RUN → RUN-Syncup, STOP → SYNCUP
Transition
Description
Effects
System state
transition
RUN-Solo → SYNCUP
The primary CPU is in the RUN operating state. The redundant system switch-
es from the RUN-Solo system state to the SYNCUP system state if:
You set the backup CPU to RUN via the PG/PC, the display or the RH_CTRL
instruction (Mode 7) and the mode selector is set to RUN
or
You switch the mode selector on the backup CPU from STOP to RUN.
or
You POWER ON the backup CPU (mode selector to RUN).
and
the SYNCUP system state is not disabled by the RH_CTRL instruction.
See section SYNCUP
system state
(Page 388)
Operating state
transitions
RUN → RUN-Syncup
The primary CPU switches from the RUN operating state to the RUN-Syncup
operating state if:
You set the backup CPU to RUN via the PG/PC or the display and the mode
selector is set to RUN
or
You switch the mode selector on the backup CPU from STOP to RUN.
or
You POWER ON the backup CPU (mode selector to RUN).
STOP → SYNCUP
The backup CPU switches from the STOP operating state to the SYNCUP oper-
ating state.