Technical specifications
CPU 1512C-1 PN (6ES7512-1CK00-0AB0)
Manual, 09/2016, A5E35306440-AB
137
6ES7512-1CK00-0AB0
Encoder signals, incremental encoder (asymme-
tric)
Input voltage
24 V
Input frequency, max.
100 kHz
Counting frequency, max.
400 kHz; with quadruple evaluation
Configurable signal filter
Yes
Incremental encoder with A/B tracks, 90° phas
ed-
shifted
Yes
Incremental encoder with A/B tracks, 90° phased
-
shifted and zero track
Yes
Pulse encoder
Yes
Pulse encoder with direction
Yes
Pulse encoder with one pulse signal per count
direction
Yes
Errors/accuracies
Linearity error (relative to input range), (+/-)
0.1%
Temperature error (relative to input range), (+/-)
0.005%/K
Crosstalk between the inputs, max.
-60 dB
Reproducibility in steady state condition at 25 °C
(relative to input range), (+/-)
0.05%
Output ripple (relative to output ra
nge, bandwidth
0 to 50 kHz), (+/-)
0.02%
Linearity error (relative to output range), (+/-)
0.15%
Temperature error (relative to output range), (+/-)
0.005%/K
Crosstalk between outputs, max.
-80 dB
Reproducibility in steady state condition at 25 °C
(relative to output range), (+/-)
0.05%
Operational limit across the entire temperature
range
Voltage, relative to input range, (+/-)
0.3%
Current, relative to input range, (+/-)
0.3%
Resistance, relative to input range, (+/-)
0.3%
Resistance
-type thermometer, relative to input
range, (+/-)
Pt100 Standard: ±2 K, Pt100 Climatic: ±1 K,
Ni100 Standard: ±1.2 K, Ni100 Climatic: ±1 K
Voltage, relative to output range, (+/-)
0.3%
Current, relative to output range, (+/-)
0.3%
Basic error limit (operational limit at 25 °C)
Voltage, relative to input range, (+/-)
0.2%
Current, relative to input range, (+/-)
0.2%
Resistance, relative to input range, (+/-)
0.2%
Resistance
-type thermometer, relative to input
range, (+/
-)
Pt100 Standard: ±1 K, Pt100 Climatic: ±0.5 K,
Ni100 Standard: ±0.6 K, Ni100 Climatic: ±0.5 K
Voltage, relative to output range, (+/-)
0.2%
Current, relative to output range, (+/
-) 0.2%